SABRE Series Inverter System
UNIPOWER LLC
3900 Coral Ridge Drive, Coral Springs, Florida 33065 UNITED STATES
Tel: +1 954-346-2442 Fax: +1 954-340-7901 Email: T[email protected]
www.unipowerco.com
www.unipowerco.com
gravitas_sabre_system-br-revl-1114.indd
Winpower PC Software
2U MANUAL BYPASS / DISTRIBUTION MODULES
The DPMBS2U and MBS2U manual bypass and power distribution modules enable the user to manually switch between inverter output or
utility output and to override the STS module for maintenance purposes. A mechanical interlock between these units and the STS module
ensures that AC to the load cannot be inadvertently interrupted.
The DPMBS2U, used with systems up to 50A output capacity, provides two means of distributing AC to the load as standard; as a single
bulk output or via eight IEC320 or NEMA outlet sockets with individual Magnetic Circuit Breakers.
The MBS2U-100 is used with systems employing the STS10048 100A STS module and provides AC through a single bulk output.
• 75A (DPMBS2U) or 125A (MBS2U-100) Bypass switch
• Enables hot-swap of STS module
• Bulk output on terminal block
AC utility can be isolated via MCB
• 100A Master MCB
• 6 x NEMA 5-15 + 2 x NEMA 50-20 outlets (DPMBS2U-N)
• 6 x IEC320-C14 + 2 x IEC320-C20 outlets (DPMBS2U-E)
• Individual CBs for each circuit on DPMBS2U models
CONTROLLER MODULE
The SABRE Series Controller, allows the user to monitor real-time system status such as output voltage, output current, alarm status, and
also allows system parameters, to quickly be changed with the touch of a few keys on the front panel. With the Communications Interface
Module installed the system can be monitored over a variety of interfaces with a local PC running Winpower.
• Compact design (1RU Height)
• Programmable Dry contact alarms (5 in total)
• RS-232, USB TCP/IP (with IFC2000)
• CAN Bus interface embedded
• Hot swappable
• RealTime Clock
• LCD and LED indicator
Audible alarm function embedded
COMMUNICATIONS INTERFACE
The SABRE Series Communications Interface provides system connection to a computer via RS232 or USB for the purposes of monitoring,
control or programming using the Winpower PC based software that provides a user friendly GUI interface.
An optional SNMP module provides alarm traps over a LAN interface.
GND
AC I/P N
AC I/P L AC O/P L
GND
AC O/P N
GND
AC I/P N
AC I/P L BULK AC O/P L
GND
BULK AC O/P N
GND
AC I/P N
AC I/P L BULK AC O/P L
GND
BULK AC O/P N
OUTLETS - 6 x NEMA 5-15 / 2 x NEMA 5-20
OUTLETS - 6 x IEC60320-13 / 2 x IEC60320-20
DPMBS2U-N connections
DPMBS2U-E connections MBS2U-100 connections
DPMBS2U
MBS2U-100
DEFINING ALTERNATE & CUSTOM SYSTEM CONFIGURATIONS
Customers can customize an inverter design to meet their application requirements and still benet from
delivery of a factory assembled and fully tested product that minimizes installation time. Customers can
choose the number of inverter shelves and types of distribution as well as adding or removing STS , MBS and
communication options.
The following shows how to build an alternate conguration part number:
IX6U-3-TS100S-D1E-120
Output Voltage, 120 for 120VAC or 230 for 230VAC
Maintenance By-Pass (MBS) & Distribution
Delete if not required, otherwise D1N, D1E, D2N, D2E or D2B
SNMP alarm trap
Delete if not required
Static Transfer Switch (STS)
Delete if not required, otherwise TS50 or TS100.
Number of inverter shelves included
1 to 6. Each shelf is 3kVA
Total height of system unit as dened by the options specied
2U to 10U (see how this is dened in the table below)
To dene a custom systems complete the following table:
STEP INSTRUCTIONS
SELECTION
OPTION
RU SELECTION RU
EXAMPLE
SELECTION RU
1
Select the number of inverter shelves
(each shelf is 3KVA)
1-6 1-6 3 3
2
Control Shelf/STS/Inverter alarm options, choose only one:
TS50S 1
NO STS and Relay Alarms leave blank 1
NO STS and SNMP Alarm trap module S 1
50A STS and Relay Alarms TS50 1
50A STS and SNMP Alarm trap module TS50S 1
100A STS and Relay Alarms TS100 2
Controller + 100A STS TS100S 2
3
Distribution Options choose only one:
D2E 2
NO Distribution leave blank 0
6 NEMA 5-15 + 1 Bulk (120V only) 100A D1N 1
6 IEC C13 + 1 Bulk (120/230V) 100A D1E 1
6 Terminal Block + 1 Bulk (120/230V) 100A D1T 1
6 NEMA 5-15/ 2 NEMA 5-20/ 1 Bulk + 75A MBS* D2N 2
6 IEC C13/ 2 IEC C19/ 1 Bulk + 75A MBS* D2E 2
1 Bulk + 125A MBS (for use with 100A STS) D2B 2
4
Place the number of RU’s for each selection 1-3 in the height column
and this total goes in selection #4 to give the system total height in RU’s
6
* Use with 50A STS
Page view 0
1 2 3 4 5 6

Summary of Contents

Page 1 - MBS2U-100

UNIPOWER LLC ● Tel: +1 954-346-2442 ● Email: [email protected] Series Inverter SystemUNIPOWER LLC3900 Coral Ridge Drive, Coral

Page 2 - Inverter Power System

UNIPOWER LLC ● Tel: +1 954-346-2442 ● Email: [email protected] LLC ● Tel: +1 954-346-2442 ● Email: Telecom-Power@un

Page 3

UNIPOWER LLC ● Tel: +1 954-346-2442 ● Email: [email protected] LLC ● Tel: +1 954-346-2442 ● Email: Telecom-Power@un

Page 4

UNIPOWER LLC ● Tel: +1 954-346-2442 ● Email: [email protected] LLC ● Tel: +1 954-346-2442 ● Email: Telecom-Power@un

Page 5

UNIPOWER LLC ● Tel: +1 954-346-2442 ● Email: [email protected] Series Inverter SystemUNIPOWER LLC3900 Coral Ridge Drive, Coral

Page 6

UNIPOWER LLC ● Tel: +1 954-346-2442 ● Email: [email protected] Series Inverter SystemUNIPOWER LLC3900 Coral Ridge Drive, Coral

Comments to this Manuals

No comments